Oct 02, 2026 - 06:00 UTC
Start time : 02/10/2026 06:00 UTC
End time : 02/10/2026 14:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Oct 2, 2026 06:00-14:00 UTC
About This Site
Welcome to the Network and Infrastructure status page for real-time information on system performance and availability.
Scheduled Maintenance
[RBX8][Infrastructure] - Rack R824A02 maintenance notification Oct 5, 2026 04:00 - Oct 6, 2026 06:00 UTC
Start time : 05/10/2026 04:00 UTC
End time : 06/10/2026 06:00 UTC
Service impact : During the maintenance window, the servers in the specified rack will be gracefully shut down to allow the maintenance activities to be performed safely. As a result, the services hosted on these servers will be unavailable before being restored once the maintenance is complete.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 24, 2026 - 13:53 UTC
[ERI1][Infrastructure] - Multiple Rack maintenance notification Oct 5, 2026 05:00 - Oct 9, 2026 16:00 UTC
List of concerned racks:
- Rack E103D01,02,04,05
- Rack E103D07,08,09,10,11,12
Start time : 05/10/2026 05:00 UTC
End time : 09/10/2026 16:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 21, 2026 - 14:33 UTC
[LIM3][Infrastructure] - Rows LIM0311A / LIM0311B maintenance notification Oct 5, 2026 05:00 - Oct 9, 2026 14:00 UTC
List of concerned racks :
- LIM0311A01B
- LIM0311A02A
- LIM0311A02B
- LIM0311A02C
- LIM0311A04B
- LIM0311A04C
- LIM0311A05A
- LIM0311A05C
- LIM0311A06A
- LIM0311A06B
- LIM0311A06C
- LIM0311B01A
- LIM0311B01B
- LIM0311B02A
- LIM0311B02B
- LIM0311B02C
- LIM0311B03A
- LIM0311B03B
- LIM0311B03C
- LIM0311B04A
- LIM0311B04C
- LIM0311B05A
- LIM0311B05C
- LIM0311B06A
- LIM0311B06B
- LIM0311B06C
Start time : 05/10/2026 05:00 UTC
End time : 09/10/2026 14:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 10, 2026 - 21:46 UTC
[ERI1][Infrastructure] - Multiple racks maintenance notification Oct 5, 2026 05:00 - Oct 9, 2026 16:00 UTC
Start time : 05/10/2026 05:00 UTC
End time : 09/10/2026 16:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
List of concerned racks:
- Rack E105C01
- Rack E105C02
- Rack E105C03
- Rack E105C04
- Rack E105C05
- Rack E105C06
- Rack E105C07
- Rack E105C08
- Rack E105C09
- Rack E105C010
- Rack E105C011
- Rack E105C012
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:45 UTC
[ERI1][Infrastructure] - Rack E104B07 maintenance notification Oct 5, 2026 05:00-11:00 UTC
Start time : 05/10/2026 05:00 UTC
End time : 05/10/2026 11:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:48 UTC
[ERI1][Infrastructure] - Multiple racks maintenance notification Oct 5, 2026 05:00 - Oct 9, 2026 16:00 UTC
Start time : 05/10/2026 05:00 UTC
End time : 09/10/2026 16:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
List of concerned racks:
- Rack E105B01
- Rack E105B02
- Rack E105B03
- Rack E105B04
- Rack E105B05
- Rack E105B06
- Rack E105B07
- Rack E105B08
- Rack E105B09
- Rack E105B010
- Rack E105B011
- Rack E105B012
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:42 UTC
[SBG3][Cooling System] - Rack S351B06 Oct 5, 2026 06:00-15:00 UTC
Sep 29, 2026 - 22:13 UTC
As part of our continuous improvement plan, we will be carrying out a maintenance on our cooling infrastructure.
Start time: 05/10/2026 06:00 UTC
End time: 05/10/2026 15:00 UTC
Service impact: During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement: As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Sep 29, 2026 - 17:00 UTC
[RBX4][Cooling System] - Rack 56D18 maintenance notification Oct 5, 2026 06:00-15:00 UTC
Start time : 05/10/2026 06:00 UTC
End time : 05/10/2026 15:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 12:47 UTC
[GRA4][Cooling System] - Rack GRA0404C02C Maintenance Notification Oct 5, 2026 06:00-14:00 UTC
Start time : 05/10/2026 06:00 UTC
End time : 05/10/2026 14:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 01, 2026 - 13:08 UTC
[RBX/GRA/LIM/ERI/BHS/VIN/HIL][Network Services] - vRack Services maintenance notification Oct 5, 2026 07:00-16:00 UTC
Start time : 05/10/2026 07:00 UTC
End time : 05/10/2026 16:00 UTC
Service impact : None
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our vRack Services.
Thank you for your understanding.
Posted on Sep 30, 2026 - 20:10 UTC
[BHS8][Cooling System] - Rack BHS0812B04C maintenance notification Oct 5, 2026 11:00-19:30 UTC
Start time : 05/10/2026 11:00 UTC
End time : 05/10/2026 19:30 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:48 UTC
[BHS8][Cooling System] - Rack BHS0813A04C maintenance notification Oct 5, 2026 11:00-19:30 UTC
Start time : 05/10/2026 11:00 UTC
End time : 05/10/2026 19:30 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:50 UTC
[RBX][Network Services] - vRack Services Maintenance Notification Oct 5, 2026 22:30 - Oct 6, 2026 06:30 UTC
Start time : 05/10/2026 22:30 UTC
End time : 06/10/2026 06:30 UTC
Service impact : None
Service improvement : As part of our continuous improvement policy, our teams will be carrying out maintenance to update multiple Network devices and improve overall Network performance.
Thank you for your understanding.
Posted on Sep 04, 2026 - 17:28 UTC
[RBX8][Infrastructure] - Rack R807R20 maintenance notification Oct 6, 2026 04:00 - Oct 7, 2026 06:00 UTC
Start time : 06/10/2026 04:00 UTC
End time : 07/10/2026 06:00 UTC
Service impact : During the maintenance window, the servers in the specified rack will be gracefully shut down to allow the maintenance activities to be performed safely. As a result, the services hosted on these servers will be unavailable before being restored once the maintenance is complete.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 24, 2026 - 13:40 UTC
[ERI1][Infrastructure] - Rack E104B08 maintenance notification Oct 6, 2026 05:00-11:00 UTC
Start time : 06/10/2026 05:00 UTC
End time : 06/10/2026 11:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:46 UTC
[GRA4][Cooling System] - Rack GRA0404C03A Maintenance Notification Oct 6, 2026 06:00-14:00 UTC
Start time : 06/10/2026 06:00 UTC
End time : 06/10/2026 14:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 01, 2026 - 13:10 UTC
[RBX4][Cooling System] - Rack 56D16 maintenance notification Oct 6, 2026 06:00-15:00 UTC
Start time : 06/10/2026 06:00 UTC
End time : 06/10/2026 15:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 12:56 UTC
[WAW1][Infrastructure] - Rack WAW0107B04A maintenance notification Oct 6, 2026 06:00-14:00 UTC
Start time : 06/10/2026 06:00 UTC
End time : 06/10/2026 14:00 UTC
Service impact : During the maintenance window, the servers in the specified rack will be gracefully shut down to allow the maintenance activities to be performed safely. As a result, the services hosted on these servers will be unavailable before being restored once the maintenance is complete.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 15, 2026 - 09:41 UTC
[LIM3][Infrastructure] - Multiple racks electrical maintenance notification Oct 6, 2026 07:00-14:00 UTC
-LIM0315E02A
-LIM0315E02B
-LIM0315E02C
-LIM0315E03A
-LIM0315E03B
-LIM0315E03C
-LIM0315D01A
-LIM0315D01B
Start time : 06/10/2026 07:00 UTC
End time : 06/10/2026 14:00 UTC
Service impact : None
Service improvement : As part of our continuous improvement policy, we will be doing an electrical maintenance in DC.
Thank you for your understanding.
Posted on Oct 01, 2026 - 20:18 UTC
[IEB01][Cooling System] - Rack IEB0101A02A maintenance notification Oct 6, 2026 08:00-18:00 UTC
Start time : 06/10/2026 08:00 UTC
End time : 06/10/2026 18:00 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:59 UTC
[BHS8][Cooling System] - Rack BHS0812B04B maintenance notification Oct 6, 2026 11:00-19:30 UTC
Start time : 06/10/2026 11:00 UTC
End time : 06/10/2026 19:30 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:52 UTC
[PAR][Network] - Backbone maintenance notification Oct 6, 2026 19:00 - Oct 7, 2026 04:00 UTC
Start time : 06/10/2026 19:00 UTC
End time : 07/10/2026 04:00 UTC
Service impact : During the maintenance, network perturbation and latency will be observed on our Point of Presence (PoP) located in Paris .
Service improvement : As part of our continuous improvement policy, our teams will be doing a maintenance on multiple network equipment.
Thank you for your understanding.
Posted on Sep 18, 2026 - 14:50 UTC
[PAR][Network] - Backbone maintenance notification Oct 6, 2026 19:00 - Oct 7, 2026 04:00 UTC
Start time : 06/10/2026 19:00 UTC
End time : 07/10/2026 04:00 UTC
Service impact : None.
Service improvement : As part of our continuous improvement policy, our teams will be doing a maintenance on multiple network equipment.
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:55 UTC
[LIM3][Infrastructure] - Multiple Rack maintenance notification Oct 7, 2026 05:00 - Oct 16, 2026 15:00 UTC
List of the concerned racks:
LIM0312A01A
LIM0312A01C
LIM0312A02A
LIM0312A02B
LIM0312A02C
LIM0312A03A
LIM0312A03B
LIM0312A04A
LIM0312A04C
LIM0312A05A
LIM0312A06A
LIM0312A06B
LIM0312A06C
LIM0312B01B
LIM0312B01C
LIM0312B02A
LIM0312B02B
LIM0312B02C
LIM0312B03A
LIM0312B03B
LIM0312B03C
LIM0312B04A
LIM0312B04B
LIM0312B05A
LIM0312B05B
LIM0312B06B
LIM0312B06C
Start time : 07/10/2026 05:00 UTC
End time : 16/10/2026 15:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 22, 2026 - 12:24 UTC
[ERI1][Infrastructure] - Rack E104B09 maintenance notification Oct 7, 2026 05:00-11:00 UTC
Start time : 07/10/2026 05:00 UTC
End time : 07/10/2026 11:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:54 UTC
[GRA4][Cooling System] - Rack GRA0404C03B Maintenance Notification Oct 7, 2026 06:00-14:00 UTC
Start time : 07/10/2026 06:00 UTC
End time : 07/10/2026 14:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 01, 2026 - 13:12 UTC
[RBX3][Cooling System] - Rack 46F17 maintenance notification Oct 7, 2026 06:00-15:00 UTC
Start time : 07/10/2026 06:00 UTC
End time : 07/10/2026 15:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 13:09 UTC
[WAW1][Infrastructure] - Rack WAW0106A02B maintenance notification Oct 7, 2026 06:00-14:00 UTC
Start time : 07/10/2026 06:00 UTC
End time : 07/10/2026 14:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 14, 2026 - 09:27 UTC
[BHS][Network] - Backbone maintenance notification Oct 7, 2026 08:00-10:00 UTC
Start time : 07/10/2026 08:00 UTC
End time : 07/10/2026 10:00 UTC
Service impact : None
Service improvement : As part of our continuous improvement policy, our teams will be doing a maintenance on multiple network equipment.
Thank you for your understanding.
Posted on Sep 29, 2026 - 14:27 UTC
[GRA3][Cooling System] - Rack GRA0328B02B Maintenance Notification Oct 7, 2026 08:00-16:00 UTC
Start time : 07/10/2026 08:00 UTC
End time : 07/10/2026 16:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Oct 02, 2026 - 16:45 UTC
[IEB01][Cooling System] - Rack IEB0101B01A maintenance notification Oct 7, 2026 08:00-18:00 UTC
Start time : 07/10/2026 08:00 UTC
End time : 07/10/2026 18:00 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 09:02 UTC
[BHS8][Cooling System] - Rack BHS0812B03C maintenance notification Oct 7, 2026 11:00-19:30 UTC
Start time : 07/10/2026 11:00 UTC
End time : 07/10/2026 19:30 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:54 UTC
[PAR][Network] - Backbone maintenance notification Oct 7, 2026 19:00 - Oct 8, 2026 04:00 UTC
Start time : 07/10/2026 19:00 UTC
End time : 08/10/2026 04:00 UTC
Service impact : During the maintenance, network perturbation and latency will be observed on our Point of Presence (PoP) located in Paris .
Service improvement : As part of our continuous improvement policy, our teams will be doing a maintenance on multiple network equipment.
Thank you for your understanding.
Posted on Sep 18, 2026 - 14:58 UTC
[ERI1][Infrastructure] - Rack E104B10 maintenance notification Oct 8, 2026 05:00-11:00 UTC
Start time : 08/10/2026 05:00 UTC
End time : 08/10/2026 11:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:50 UTC
[WAW1][Infrastructure] - Rack WAW0106B02C maintenance notification Oct 8, 2026 06:00-14:00 UTC
Start time : 08/10/2026 06:00 UTC
End time : 08/10/2026 14:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 14, 2026 - 11:09 UTC
[RBX3][Cooling System] - Rack 46F29 maintenance notification Oct 8, 2026 06:00-15:00 UTC
Start time : 08/10/2026 06:00 UTC
End time : 08/10/2026 15:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 13:24 UTC
[GRA4][Cooling System] - Rack GRA0404C03C Maintenance Notification Oct 8, 2026 06:00-14:00 UTC
Start time : 08/10/2026 06:00 UTC
End time : 08/10/2026 14:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 01, 2026 - 13:14 UTC
[YYZ01][Infrastructure] - Electrical maintenance notification Oct 8, 2026 11:00-20:00 UTC
Start time : 08/10/2026 11:00 UTC
End time : 08/10/2026 20:00 UTC
Service impact : None
Service improvement : As part of our continuous improvement policy, we will be doing an electrical maintenance in YYZ01.
Thank you for your understanding.
Posted on Sep 24, 2026 - 13:07 UTC
[BHS8][Cooling System] - Rack BHS0812B03B maintenance notification Oct 8, 2026 11:00-19:30 UTC
Start time : 08/10/2026 11:00 UTC
End time : 08/10/2026 19:30 UTC
Service impact : During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 13, 2026 - 08:56 UTC
[RBX8][Cooling System] - Rack R807L27 maintenance notification Oct 9, 2026 04:00-15:00 UTC
Start time : 09/10/2026 04:00 UTC
End time : 09/10/2026 15:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 24, 2026 - 12:59 UTC
[RBX4][Cooling System] - Rack 54B19 maintenance notification Oct 9, 2026 06:00-15:00 UTC
Start time : 09/10/2026 06:00 UTC
End time : 09/10/2026 15:00 UTC
Service impact : The cooling system's efficiency could be temporarily impacted for some servers, which could cause a decreased performance during this maintenance.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 13:31 UTC
[RBX8][Infrastructure] - Rack R824A07 maintenance notification Oct 12, 2026 04:00 - Oct 13, 2026 06:00 UTC
Start time : 12/10/2026 04:00 UTC
End time : 13/10/2026 06:00 UTC
Service impact : During the maintenance window, the servers in the specified rack will be gracefully shut down to allow the maintenance activities to be performed safely. As a result, the services hosted on these servers will be unavailable before being restored once the maintenance is complete.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 28, 2026 - 20:12 UTC
[ERI1][Infrastructure] - Multiple Rack maintenance notification Oct 12, 2026 05:00 - Oct 16, 2026 16:00 UTC
List of concerned racks:
- Rack E105B01,02,03
- Rack E105B04,05,06
- Rack E105B07,08,09
- Rack E105B10,11,12
Start time : 12/10/2026 05:00 UTC
End time : 16/10/2026 16:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 21, 2026 - 14:12 UTC
[LIM3][Infrastructure] - Multiple racks maintenance notification Oct 12, 2026 05:00 - Oct 16, 2026 15:00 UTC
List of concerned racks :
-LIM0313A01B
-LIM0313A01C
-LIM0313A02B
-LIM0313A02C
-LIM0313A03A
-LIM0313A03B
-LIM0313A04A
-LIM0313A04B
-LIM0313A04C
-LIM0313A05A
-LIM0313A05B
-LIM0313A05C
-LIM0313B01A
-LIM0313B01B
-LIM0313B01C
-LIM0313B02A
-LIM0313B02B
-LIM0313B02C
-LIM0313B03A
-LIM0313B03B
-LIM0313B03C
-LIM0313B04A
-LIM0313B04C
-LIM0313B05A
-LIM0313B05B
-LIM0313B06A
-LIM0313B06B
-LIM0313B06C
Start time : 12/10/2026 05:00 UTC
End time : 16/10/2026 15:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 22, 2026 - 20:42 UTC
[ERI1][Infrastructure] - Multiple racks maintenance notification Oct 12, 2026 05:00 - Oct 16, 2026 16:00 UTC
Start time : 12/10/2026 05:00 UTC
End time : 16/10/2026 16:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
List of concerned racks:
- Rack E105C01
- Rack E105C02
- Rack E105C03
- Rack E105C04
- Rack E105C05
- Rack E105C06
- Rack E105C07
- Rack E105C08
- Rack E105C09
- Rack E105C010
- Rack E105C011
- Rack E105C012
Thank you for your understanding.
Posted on Sep 18, 2026 - 13:53 UTC
[LIM3][Infrastructure] - Multiple Rack maintenance notification Oct 12, 2026 05:00 - Oct 23, 2026 15:00 UTC
List of the concerned racks:
LIM0314A01B
LIM0314A02A
LIM0314A02C
LIM0314A03A
LIM0314A03B
LIM0314A03C
LIM0314A04A
LIM0314A04B
LIM0314A04C
LIM0314A05A
LIM0314A05B
LIM0314A05C
LIM0314A06B
LIM0314A06C
LIM0314B01A
LIM0314B01B
LIM0314B01C
LIM0314B02A
LIM0314B02B
LIM0314B02C
LIM0314B03A
LIM0314B03B
LIM0314B03C
LIM0314B04B
LIM0314B04C
LIM0314B05A
LIM0314B05B
LIM0314B05C
LIM0314B06A
LIM0314B06B
Start time : 12/10/2026 05:00 UTC
End time : 23/10/2026 15:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 22, 2026 - 12:37 UTC
[DC][Infrastructure] - Rack E104B11 maintenance notification Oct 12, 2026 05:00-11:00 UTC
Start time : 12/10/2026 05:00 UTC
End time : 12/10/2026 11:00 UTC
Service impact : Customers could still experience a temporary reboot or shutdown in the worst case of their servers.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our electrical infrastructure.
Thank you for your understanding.
Posted on Sep 21, 2026 - 09:46 UTC
[SBG5][Cooling System] - Rack SBG0506A02D Oct 12, 2026 06:00-15:00 UTC
Sep 29, 2026 - 22:15 UTC
As part of our continuous improvement plan, we will be carrying out a maintenance on our cooling infrastructure.
Start time: 12/10/2026 06:00 UTC
End time: 12/10/2026 15:00 UTC
Service impact: During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement: As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Sep 29, 2026 - 17:00 UTC
[SBG3][Cooling System] - Rack S350B01 Oct 12, 2026 06:00-15:00 UTC
Sep 29, 2026 - 22:17 UTC
As part of our continuous improvement plan, we will be carrying out a maintenance on our cooling infrastructure.
Start time: 12/10/2026 06:00 UTC
End time: 12/10/2026 15:00 UTC
Service impact: During this maintenance, the cooling system's efficiency may be temporarily reduced for some servers, potentially lowering performance. Despite ongoing mitigation efforts, customers could still experience a temporary reboot or shutdown in the worst case.
Service improvement: As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Sep 29, 2026 - 17:00 UTC
[GRA4][Cooling System] - Rack GRA0404D03A Maintenance Notification Oct 12, 2026 06:00-14:00 UTC
Start time : 12/10/2026 06:00 UTC
End time : 12/10/2026 14:00 UTC
Service impact : During this maintenance, the servers in the affected rack will be gracefully shut down beforehand. Customers hosted on these servers should expect a planned service interruption for the duration of the maintenance window.
Service improvement : As part of our continuous improvement policy, we will be doing a maintenance on our cooling infrastructure.
Thank you for your understanding.
Posted on Sep 01, 2026 - 13:17 UTC