FS#9962 — Main electrical supply
Scheduled Maintenance Report for Network & Infrastructure
Completed
We have a power cut on the main supply to Roubaix 1 and 3.
The generators have taken over.

Update(s):

Date: 2014-01-04 12:39:29 UTC
ERDF has just performed to the manipulation to get back to normal.
We heard yesterday that the problems come from a mini-tornado that went on towns: Leers / Crois / Wattrelos. Sheet roof flew and hit the 225 kV lines causing failure.

We are on the normal pattern, end of the incident.


Date: 2014-01-03 22:05:07 UTC
ERDF will not get back to normal before tomorrow morning.
The meeting was arranged for 9am.

GE, which has not started has been repaired: batteries defected (however they were replaced last year during preventive maintenance ...).
The main GE of Roubaix 1 is again available in N+1 in case of another cut-off tonight.

Date: 2014-01-03 22:02:00 UTC
We switched back the GE to the relief cable shortly after the cut-off.
There was no impact on the servers.

One of the 5 GE f this site is faulty.
The manufacturer is there to fix the issue.

We contacted ERDF who will recontact us to return to the \"normal\" cable.
Posted Jan 03, 2014 - 17:07 UTC