FS#10909 — EDF
Scheduled Maintenance Report for Network & Infrastructure
Completed
EDF was shut down briefly.
No impact on the servers thanks to the UPS devices and generators.

The EDF power supply switched to EMERGENCY instead of NORMAL and remains on emergency at present.

We will return to EDF, and this ERDF will intervene within a few hours in order to return to NORMAL.


Update(s):

Date: 2014-06-06 08:51:49 UTC
The circuit was switched back to NORMAL this morning.

Date: 2014-06-05 16:33:40 UTC
ERDF has identified the fault: a cable pulled out in the street. This cable was repaired this morning.

There has been an impact on the source post with damaged cells resulting from the cable being pulled out.
ERDF wanted to leave us on emergency until Tuesday but we refused.

The cable will be back on NORMAL at 10:00 tomorrow morning, a meeting was held with an ERDF agent.

Date: 2014-06-05 09:20:37 UTC
The return to EDF-emergency went smoothly.
ERDF declares incidents in progress in our Roubaix area. Expected time for incident resolution: 12hrs.

We will remind ERDF about going back onto NORMAL early in the afternoon.
The generators are available again in emergency mode.
Posted Jun 05, 2014 - 09:12 UTC