We are going to do a modification on the transformer 2 of RBX 2 in order
to improve the transformer's detection default.
For this purpose we need to do several switch attempts to the
spare transformer.
Update(s):
Date: 2012-07-27 13:40:47 UTC We have validated the new solution.
Date: 2012-07-27 13:38:05 UTC We will make a modification on this TGBT in order to avoid a hard point
on the interlocking cables of normal/rescue.
Therefore, we will switch to the rescue transformer.
Date: 2012-07-23 09:55:09 UTC We start with tests.
Date: 2012-07-17 21:39:42 UTC The return to NORMAL was done.
We will do the working soon again on this transformer / TGBT to validate the new funtionalities.
Date: 2012-07-17 10:37:04 UTC This morning we switched to a new rescue transformer but in a preventive manner
to add a box for extra protection on this sec transformer.
Back to NORMAL expected this after noon.
Date: 2012-07-17 10:36:16 UTC This morning we switched to a new rescue transformer but in a preventive manner
to add a box for extra protection on this sec transformer.
Back to NORMAL expected this after noon.
Date: 2012-07-10 08:06:43 UTC The problem of switching normal/rescue has been corrected by the technician.
We are currently on the rescue to make the changes on the
fault detection of the normal transformer.
Date: 2012-07-10 08:05:12 UTC We encountered some problems on switching due to
interlocks between the normal circuit breaker and the rescue circuit breaker.
The technician is here this morning to solve these problems.
We will make new switches again. Inverters,
that we tested the autonomy, will render this work invisible.