FS#4426 — Roubaix internal network routing

Scheduled Maintenance Report for Network & Infrastructure

Completed

We are switching the internal routing network on a new infra.


Update(s):

Date: 2010-07-30 23:29:14 UTC
regarding the commercial speech, we arrive to the reality which is totally different ...

http://www.cisco.com/en/US/docs/switches/datacenter/sw/5_x/nx-os/interfaces/configuration/guide/if_basic.html#wp2094156

80Gbps are divided by 8x (4x10G) where the 4 ports 10G are sharing a 10G of the backplane. This is not what we have been told, comparing to the contexts we had presented for Ovh.

That's tiring.



Date: 2010-07-30 23:22:51 UTC
vss-1 and rbx-1 have some communicating problems with other routers. We believe the bandwidth is limited on the pull of port 10G on the router's card (4x20G). we are going to replace ports on the card to use all available bandwidth.

It's quite strange, since the traffic does not go to backplane and remains on the card. So normally we should not face that problem ...

We are still going to manipulate then we will see.

Date: 2010-07-30 23:13:51 UTC
Done.

We have also changed the MTU in order to find the 9216 instead of 9200 because of a bug on nexus 5000:

http://status.ovh.co.uk/?do=details&id=346

On nexus 7000 it works. So the problem was really there (we did not guess)


Date: 2010-07-30 23:10:48 UTC
rbx-99

Date: 2010-07-30 23:10:41 UTC
vss-3

Date: 2010-07-30 23:10:35 UTC
vss-2

Date: 2010-07-30 23:10:29 UTC
vss-1

Date: 2010-07-30 23:10:18 UTC
Same for rbx-2

Date: 2010-07-30 23:10:02 UTC
We are switching rbx-1
Posted Jul 30, 2010 - 23:09 UTC