Get webhook notifications whenever Network & Infrastructure creates an incident, updates an incident, resolves an incident or changes a component status.
Jun 12 03:26:47 rbx-0-c1.routers.ovh.net 2010 Jun 12 01:26:29 %SYS-3-EOBC_CHANNELHUNG:Ethernet out of band channel on module 8 is faulty. Module has been powered down!
Jun 12 03:26:46 rbx-0-c1.routers.ovh.net 2010 Jun 12 01:26:28 %SYS-3-EOBC_POWERDOWN:Ethernet out of band channel fault detected. Systematically shutting down modules to identify the faulty module
Jun 12 03:18:50 rbx-0-c1.routers.ovh.net 2010 Jun 12 01:18:33 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739750
Jun 12 03:18:50 rbx-0-c1.routers.ovh.net 2010 Jun 12 01:18:33 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415954
Jun 12 02:56:36 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:56:20 %IP-3-TCP_BADCKSUM:TCP bad checksum
Jun 12 02:48:22 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:48:05 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739749
Jun 12 02:48:22 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:48:05 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415947
Jun 12 02:36:56 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:36:40 %IP-3-TCP_BADCKSUM:TCP bad checksum
Jun 12 02:17:54 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:17:37 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739745
Jun 12 02:17:54 rbx-0-c1.routers.ovh.net 2010 Jun 12 00:17:37 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415936
Jun 12 01:47:26 rbx-0-c1.routers.ovh.net 2010 Jun 11 23:47:09 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739743
Jun 12 01:47:26 rbx-0-c1.routers.ovh.net 2010 Jun 11 23:47:09 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415926
Jun 12 01:16:59 rbx-0-c1.routers.ovh.net 2010 Jun 11 23:16:42 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739738
Jun 12 01:16:59 rbx-0-c1.routers.ovh.net 2010 Jun 11 23:16:42 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415914
Jun 12 00:46:31 rbx-0-c1.routers.ovh.net 2010 Jun 11 22:46:14 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP checksum error counter = 739734
Jun 12 00:46:31 rbx-0-c1.routers.ovh.net 2010 Jun 11 22:46:14 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP too short error counter = 10052
Jun 12 00:46:31 rbx-0-c1.routers.ovh.net 2010 Jun 11 22:46:14 %SYS-4-SUPERVISOR_ERR:Forwarding engine IP length error counter = 415903
Update(s):
Date: 2010-06-12 07:37:57 UTC Tous les liens sont ups
Date: 2010-06-12 04:41:33 UTC La carte est remplacée mais 7 des liens ne remontent pas pour l'instant.